Use Example (Utilization Of Clock Data) - Mitsubishi Electric F930GOT-BWD-E User Manual

Graphic operation terminal
Hide thumbs Also See for F930GOT-BWD-E:
Table of Contents

Advertisement

Graphic Operation Terminal F930GOT
13.6.7

Use example (utilization of clock data)

The clock data built in the F930GOT can be transferred to a data register in the PLC for later
utilization while a specified bit device is ON. The clock data built in the F930GOT is stored in
the following registers. However, only the GOTR-PACK can handle these registers.
GD0: Current time (second)
GD2: Current time (hour)
GD4: Current time (month)
GD6: Current time (day of week)
Example: When the clock data (year, month, day, hour, minute and second) is transferred to
the register D100 in the PLC at every 30 seconds while M10 is ON
Select "Observe Status" in the screen creation software.
1) Select "Project", and set the cycle to 30 seconds.
2) Set the trigger 1 to "M10, ON".
3) Select "Word Set (16-bit)" as the operation, and set the number of points to "7".
4) Set "Storing Device" to "D100", "Fixed" to "0" and "Indirect Device" to "GD0".
5) Set the transfer method to "BM0V".
When this data is transferred to the F930GOT, the current time is stored in D100 at every 30
seconds while M100 is ON.
Additional Functions (in V.2.00 or later) 13
GD1: Current time (minute)
GD3: Current time (day)
GD5: Current time (year)
13-22

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents