Graphic Operation Terminal GOT-F900
12.2.1

Set item

1) Window display (comment window display)
• In FX-PCS-DU/WIN-E
If "window display" is selected as the alarm notification method, when an alarm device
turns ON, an alarm message corresponding to that device is displayed on the user
screen.
• Using the screen creation software, alarm messages can be created and alarm display
positions can be selected from upper, medium and lower.
• This window is displayed in screen mode (while a user screen is displayed).
When the display is changed to a system screen (alarm mode), the window disappears.
However, if an alarm device is ON, the window is displayed again when the display is
changed to a user screen again.
• In GT Designer
By setting "Detail Display Destination" in "Basic Setting" in "Alarm History Common
Setting" in the software to "Comment Window", detailed comment messages
corresponding to alarm devices can be displayed.
In this case, the object "Alarm History" or "Alarm List" is displayed on the user screen,
and detailed comment messages are displayed when a touch key whose key code has
been set to "FFB8 (detail display)" is pressed.
Alarm history display : Refer to Paragraph 18.5.10.
Alarm list display
• An alarm message can be displayed in up to 10
full-width or 20 half-width characters.
Upper
• When two or more alarm devices have turned
ON, the alarm messages can be scrolled using
Medium
the message scroll keys.
When two or more errors have occurred in the
Lower
system, the error messages are displayed in the
same way.
Message
• When alarm devices have turned OFF, the
scroll key
window is closed.