17.3

Observe status cycle

Set the cycle at which the GOT monitors whether the specified triggers are realized.
Select "always" or "constant cycle".
• Always:
Every time communication is performed between the GOT and the PLC, the GOT monitors
whether the specified triggers are realized. (every 200 to 300 ms.)
• Constant cycle: The cycle can be set from 1 to 60 seconds with an increment of 1 second.
At the set cycle, the GOT monitors whether the specified triggers are realized.
17.4

Setting the triggers

Set the triggers to be monitored.
Up to two bit devices can be set.
• Trigger 1: Set ON or OFF of a bit device.
• Trigger 2: Set ON or OFF of a bit device.
- When trigger 1 and trigger 2 are set, the GOT performs the operation described in the
next paragraph only when both triggers are realized.
Example: Trigger 1: "ON" is set.
- Make sure to set trigger 1. and set trigger 2 if necessary.
Applicable version
SW1D5C-GOTR-PACK(C) or later
Trigger 2: "OFF" is set.
Both triggers are realized.
Version
V2.00 or later
V3.10 or later
V1.00 or later
V2.50 or later
ON
OFF
ON
OFF
Observe status function 17
17-2