Graphic Operation Terminal GOT-F900
12.3

Alarm function in alarm mode

In alarm mode, the alarm function described below is offered.
u u u u Basic operation
SELECT MODE
screen is displayed.
Paragraph 7.3
[ ALARM MODE screen ]
[ ALARM MODE ]
DISPLAY STATUS
DISPLAY HISTORY
DISPLAY FREQUENCY
CLEAR HISTORY
a) DISPLAY STATUS
Displays the list of messages corresponding to alarm devices which are ON currently.
Alarm devices in the ON status can be reset from the GOT.
b) DISPLAY HISTORY
Stores and displays alarm occurrence date/time and alarm messages in the order of
occurrence.
Up to 1,000 alarms can be stored.
c) DISPLAY FREQUENCY
Stores the number of each alarm device turns ON, and displays the frequency in the
order of alarm device No.
Up to 32,767 cases can be stored.
d) CLEAR HISTORY
Clears all of the alarm history and the alarm frequency.
The system screens a) to d) (Nos. 1008 to 1011) can be displayed also in the screen mode.
SELECT MODE
ALARM MODE
screen is displayed.
Select "ALARM
The screen shown
MODE".
below is displayed.
END
a)
b)
c)
d)
Alarm Mode 12