Selection Of Main Circuit Wiring Equipment And Standard Cable Sizes - Toshiba VFS5 Series Operation Manual

Table of Contents

Advertisement

Selection of Main Circuit Wiring Equipment and Standard Cable Sizes

* Molded case
Drive
circuit breaker (FLA x 1.25)
(MCCB)
Model
Amp
Number
rating
(A)
S5-5020
15
S5-5030
15
S5-5040
15
S5-5060
15
S5-5120
30
S5-5160
35
S5-5220
50
S5-5270
60
*
A customer supplied disconnect means must be provided in the motor branch circuit which
supplies power to the drive. It can be separate for use with customer supplied fuses or it can
be an integral part of a customer supplied 3-pole circuit breaker (see 1996 NEC Article 430-103
through 430-113). All drives in this series are rated for output short circuit fault currents of
200,000A. The selection of MCCB (molded case circuit breaker) for this table is in accordance
with 1996 NEC Article 430-51, 430-52, 430-152, and 240-6.
**
Wire sizing is based upon NEC table 310-16 or CEC Table 2 using 75 deg C cable, an ambient
of 30 deg C, cable runs for less than 300 FT., and copper wiring for not more than three
conductors in raceway or cable or earth (directly buried). The customer should consult the NEC
or CEC wire Tables for his own particular application and wire sizing.
***
Use two parallel conductors instead of a single conductor (this will allow for the proper wire
bending radius within the cabinet). Use separate conduits for routing parallel conductors.
This prevents the need for conductor derating (see note 3 page 17).
C A U T I O N
C A U T I O N
See next page for notes.
TOSHIBA
Ampacity
Main power
and
(A)
motor load
3
#14
4
#14
5
#14
8
#14
15
#14
22
#12
28
#10
34
#10
Turn off power to the drive before making any wiring
changes to the analog output circuits.
Use separate conduits for routing incoming power, power
to motor, and control conductors. Use no more than three
power conductors and a ground conductor per conduit.
16
** Typical cable size (AWG)
Frequency command input,
frequency meter, ammeter
3-core shield cable
(speed reference)
2-core shield cable
#20
Other
signal
circuits
#18

Hide quick links: