12.93
247
Default value
0000
By setting bits 0 to 5, it is possible to invert the function of the appropriate messages (MD 241
to MD 246). In bits 8 and 9, it is possible to choose between sign-specific or absolute-value-
based interrogation of the memory address limit values (MD 185, MD 190).
Value table:
Bit 0
Programmable message 1 inverted
Bit 1
Programmable message 2 inverted
Bit 2
Programmable message 3 inverted
Bit 3
Programmable message 4 inverted
Bit 4
Programmable message 5 inverted
Bit 5
Programmable message 6 inverted
Bits 6-7
Not assigned
Bit 8
Sign evaluation monitoring 1
Bit 9
Sign evaluation monitoring 2
Bits 10-15 Not assigned
254
Default value
Display of low word in drive control word.
Value table:
Bit 0
ZK1 reset
Bit 1
Parking axis
Bit 2-6
Not assigned
Bit 7
Ramp-function generator active
Bit 8
Not assigned
Bit 9
Ramp-function generator rapid stop
Bit 10
2nd torque limit
Speed setpoint smoothing
Bit 11
Bit 12-15
Not assigned
©
Siemens AG 1992 All Rights Reserved
SINUMERIK 840C (IA)
Control word message
Lower input limit
Upper input limit
0000
Display of active functions 1
Lower output limit
Upper output limit
6FC5197- AA50
7 Drive Machine Data (SIMODRIVE Drive MD)
7.1.2 MSD MD (data description - SW 3)
Units
FFFF
Hex
0001H
0002H
0004H
0008H
0010H
0020H
0040H
0080H
Units
Hex
0: Not active
1: Active
Active
at once
Active
at once
7–37