Option Fault Monitors U6-98 And U6-99; Option Compatibility - YASKAWA SI-EP3 Technical Manual

Ac drive option. profinet
Hide thumbs Also See for SI-EP3:
Table of Contents

Advertisement

Code
Name
oFA30 to
Option Card Connection Error
oFA43
(CN5-A)
oFb00
Option Not Compatible with Port
oFb02
Option Fault
oFC00
Option Fault (CN5-B)
oFC02
Option Fault

Option Fault Monitors U6-98 and U6-99

The option can declare error/warning conditions via drive monitor parameters on the drive keypad as shown in
Table
10.1.
Fault Condition
No Fault
Force Fault
Network Link Down
Network Failure
Default MAC Address
No IP Address
No Station Name
Bad Station Name Programmed
Init. Failure
Permanent Communication Loss
Bad IP Configuration
Two drive monitor parameters, U6-98 and U6-99 assist in network troubleshooting:
• U6-98: Shows the first declared fault since the last power cycle. Only cleared upon drive power-up.
• U6-99: Shows the present option SI-EP3 status. Cleared upon a network-issued fault reset and upon power-up.
If another fault occurs while the original fault is still active, parameter U6-98 retains the original fault value and
U6-99 stores the new fault status value.

Option Compatibility

You can connect a maximum of 3 options at the same time depending on the type of option.
Note:
You can only connect one option to the GA500 and HV600. Connect the option to the CN5 connector.
Option
PG-B3, PG-X3
*2 *3
*2 *3
PG-RT3
, PG-F3
DO-A3, AO-A3
SI-C3, SI-N3, SI-P3, SI-S3, SI-T3, SI-ET3,
SI-ES3, SI-B3, SI-M3,
*3
*3
*3
SI-W3
, SI-EM3
, SI-EN3
, SI-EP3,
*4
*4
AI-A3
, DI-A3
*1
To connect two PG options, use the CN5-C and CN5-B connectors. To connect only one PG option, use the CN5-C connector.
YASKAWA SIEP C730600 89E PROFINET Technical Manual
A fault occurred in the option.
The option connected to connector CN5-B is not
compatible.
An option of the same type is already installed in
option port CN5-A, CN5-B, or CN5-C.
The option connected to connector CN5-C is not
compatible.
An option of the same type is already installed in
option port CN5-A, CN5-B, or CN5-C.
Table 10.1 Option Fault Monitor Descriptions
Status
Fault Declared
Value (U6-
98/U6-99)
N/A
0
EF0
3
bUS
1300
bUS
1301
None
1303
None
1304
None
1305
None
1306
None
1307
bUS
1308
None
1309
Table 10.2 Option Compatibility
Causes
1.
2.
3.
Connect the option to the correct connector.
• Use connector CN5-A when you connect the option.
To use other options, refer to those option manuals.
Connect the option to the correct option port.
Connect the option to the correct connector.
• Use connector CN5-A when you connect the option.
To use other options, refer to those option manuals.
Connect the option to the correct option port.
No Fault
Network sent a message to force this node to the fault state.
No network link to option board.
Connection with PLC Timeout.
Factory default MAC Address programmed into the option. Return for reprogramming.
No IP Address has been programmed into the option.
No Station Name has been programmed into the option.
Station Name Programmed is invalid and must be reprogrammed.
Initialize error on power-up.
Fatal error in MAC/PHY hardware Cycle power.
Invalid IP/subnet/gateway address programmed into F7-01 - F7-12.
Connector
CN5-B, C
CN5-C
CN5-A, B, and C
CN5-A
10 Troubleshooting
Possible Solutions
De-energize the drive.
Make sure that the option is correctly connected to the
connector.
If the problem continues, replace the option.
Description
Number of Options Possible
*1
2
1
1
1
51