USE PARTITION DESCRIPTORS

2*19
1 = partition descriptors will be programmed. If enabled, the normal
keypad display will include a partition number and four-character
descriptor).
0 = cause the keypads to display a non-partitioned system type of
display (no partition number will appear).

ENABLE J7 TRIGGERS BY PARTITION

2*20
(partition-specific)
1 = enable for displayed partition
0 = disable for displayed partition
SUPERVISION PULSES FOR
2*21
TRIGGER OUTPUTS
1 = enable pulses for each type of trigger (burglary, fire, silent panic).
This option causes the control to send periodic short pulses on the J7
radio triggers These pulses are used by the transmitter to determine
that its connection to the control is still intact.
0 = not desired
Used for supervised connection to applicable Long Range Radio
transmitters.
DISPLAY FIRE ALARMS OF OTHER PARTITIONS
2*22
(partition-specific)
1 = allow fire alarms that occur on other partitions to be displayed at
this partition's keypads.
0 = otherwise
DISPLAY BURGLARY & PANIC ALARMS OF OTHER
2*23
PARTITIONS
1 = allow burglary and panic alarms that occur on other partitions to be
displayed at this partition's keypads.
0 = otherwise
DISPLAY TROUBLES OF OTHER PARTITIONS
2*24
(partition-specific)
1 = allow troubles that occur on other partitions to be displayed at this
partition's keypads.
0 = otherwise
(partition-specific)
[1]
[1]
[000]
| |
F B S
[1]
[1]
[1]