RF TX LOW BATTERY REPORT ENABLE

1*29
1 = a trouble message for RF transmitter low battery conditions sent to
the central station.
0 = no report for transmitter low battery is desired. Note that a trouble
message will be sent for a transmitter supervision failure
independent of this selection.
RF RCVR SUPERVISION CHECK-IN INTERVAL
1*30
02-15 times 2 hours
00
If selected, failure of a receiver to receive any RF signal within the time
entered will result in activation of the response type programmed for
zone 990 for the first receiver and zone 988 for the second receiver and
their related communication reports.
RF TRANSMITTER CHECK-IN INTERVAL
1*31
02-15 times 2 hours
00
If selected, failure of an individual transmitter to send a supervision
signal within the time entered will result in a trouble response and
related communication report.

RECEIVER TYPE

1*32
0 = none
1 = using 4281 series receivers
2 = using 5881 series receivers
MULTIFREQUENCY DIALLING W/ PULSE DIAL BACKUP
1*33
1 = enable pulse dial back-up dialling if communicator is not successful
in dialling using multifrequency DTMF on first attempt.
0 = this option is not desired
COMM. SPLIT REPORT SELECTION
1*34
0 = split reporting disabled
1 = alarm, alarm restore & cancel reports sent to primary Telecom
number, all others to secondary Telecom number
2 = open/close & test reports sent to secondary Telecom number and all
other reports to primary.
This field allows certain reports to be directed to either the primary or
secondary phone number. See *51 for split/dual reporting comments.
LOW BATTERY TEST INTERVAL
1*35
1 = 1.5 second test every 50 seconds (Norwegian requirement)
0 = 13 second test every 4 minutes (ANPI requirement)
CPU FAIL TRIGGER OUTPUT
1*36
1 = yes, Output trigger 2 on J7 to be CPU fail output, overriding any
other selection for Output 2 (CENELEC requirement)
0 = no, normal use for Output 2
TLM INPUT ON ZONE 9
1*37
1 = yes, telephone line fault monitor output to be fed into zone 9
0 = no, normal use for zone 9
USER RESET OF TAMPER ALARMS INSTEAD
1*38
OF INSTALLER ONLY RESET
1 = yes
0 = no (ANPI requirement)
= the check-in monitoring interval in 2-hour
increments (4-30 hours).
= disable receiver supervision
= the check-in monitoring interval in 2-hour
increments (4-30 hours)
= disables transmitter supervision
[0]
[06]
[12] |
[0]
[0]
[0]
[0]
[0]
[0]
[0]