010 SMART CONTACT
1 = YES
0 = NO
10
V-PLEX RELAY?
1 = YES
0 = NO
010 CONS ECP ADDR
(01-31)
01
010 ACS ZONE NO
(00-31)
01
010 LOOP #
1
010 LEARN S/N?
1 = YES, 0 = NO
1
010 INPUT S/N
Axxx-xxxx
010 INPUT S/N
A022-4064
If the serial and loop number combination is already present in the system, the keypad will sound a
single long beep and display the word "DUPLICATE" along with the serial number, and the number
of the zone containing the serial/loop number combination.
If input type 6 was selected, this prompt will be displayed. Enter 1
for devices that monitor maintenance signals (ex. 5192SD,
5192SDT, 5808). Otherwise, enter 0.
If input type 6 was selected, this prompt will be displayed. Enter 1
if using 4208UXM or 4101SN relay module for this zone.
Otherwise, enter 0.
If input type 09 was selected, this prompt will be displayed. Enter
the ecp address of the keypad that is being used for entry/exit for
this access point (01-31).
If input type 10 was selected, this prompt will be displayed. Enter
the Passpoint ACS zone ID that this Vista zone maps to (00-31).
Press [*] to continue.
The cursor should now be flashing on the loop number. The default
is "1." To accept this, press [*]. If a different loop number is being
used on this device, enter the loop number (1-4) and press [*] to
continue.
(Refer to the transmitter's instructions for loop
numbers.) The loop number must be entered here, whether
using Zone Programming or Sequential Mode to enroll
serial numbers.
If you want to delete the serial number, enter
"0" and press [*]. The system will then prompt, "DELETE S/N?"
Press the "1" (YES) key to complete the delete sequence.
process deletes the serial number only, not the loop number. The
assumption is that the proper loop number was programmed, but
the wrong serial number was enrolled.
If the device's serial number has not been previously "enrolled," you
may enter the enrollment mode now by either entering "1" (YES) or
by pressing the upper left-hand button of the programme tool. If
using the programme tool, move to the physical location of
the device to be enrolled before pressing the button.
single short beep will verify that the button has been pressed. The
system will respond to the first serial number transmitted after the
"1" key on the keypad or the button of the programme tool is
pressed. Enter "0" (NO) to enroll later. (If "0" is entered, the
system will advance to the summary screen prompt.)
This prompt is displayed if "1" (YES) is entered in response to the
"Learn S/N?" prompt. The serial number may be enrolled by one of
two methods:
a) Enter the 7-digit serial number printed on the device using an
alpha keypad, OR
b) Activate the device (e.g., press a button, open or close a door,
etc.).
The system will enroll the serial number of the first device heard.
This