01 Start: Zn LIST
No list
01 Start: Zn Typ
Choices For Start/Stop Zone Types
00 = No Response (Not Used)
01 = Entry/Exit #1
02 = Entry/exit #2
03 = Perimeter
04 = Interior Follower
05 = Trouble Day/Alarm Night
06 = 24 Hr Silent
07 = 24 Hr Audible
08 = 24 Hr Aux
09 = Fire Alarm or Trouble
10 = Interior w/Delay
19 = 24 Hour Trouble
23 = No Alarm Response
(for output relay activation, such
as for access control purposes)
26 = Verified Alarm
27 = Access Point
28 = ACS MLB Supervision Fail
01 Start Part
01 Stop: Zn LIST
No list
01 Stop: Zn Typ
01 Stop Part
Relay Group
Restriction
1=yes 0=no
A Zone List is a set of zones that can be used to initiate the start or
stop relay action. If a zone list is being used to start this relay action,
enter the Zone List number 01-15. If a zone list is not being used,
enter 00. Press
A Zone Type/System Operation can be used instead of an Event/Zone
List combination to start the relay action. If a Zone Type/System
Operation is being used, enter the 2-digit code as listed below. Press
to continue.
Choices For Start/Stop System
Operation:
20 = Arming-Stay
21 = Arming-Away
22 = Disarming (Code+Off)
31 = End of Exit Time
32 = Start of Entry Time
33 = Any Burglary Alarm
34 = Code + # + 71 Key Entry
35 = Code + # + 72 Key Entry
36 = At Bell Timeout **
37 = 2 Times Bell Timeout**
38 = Chime
39 = Fire Alarm
40 = Bypassing
41 = AC Power Fail
42 = System Battery Low
If using options 56 and/or 57 (usually as the STOP Zone Type), data fields 1*74
and 1*75 for the respective relay timeouts for minutes and seconds must be
programmed.
If the starting event will be limited to occurring on a specific
partition, enter the partition number (1-8) in which the start event
will occur. Enter 0 for any partition. Press
If a zone list is being used to stop this relay action, enter the zone list
number 01-15.
the relay. If a zone list is not being used, enter 00. Press
If a Zone Type/System Operation is being used to stop the relay
action, enter the 2-digit code as listed in the start Zone Type/System
Operation prompt paragraph. Press
This is the partition to which the stop condition will be limited. Enter
0 for any partition. Enter 1-8 for specific partition number. Press
.
Relays may be grouped for common activation by time driven events
(commands 06-10--see Section 20: SCHEDULING OPTIONS for more
information). Enter 0 (no group) or 1-8 for a specific group number.
Press
to continue.
The system may have some devices which are not intended to be
under end user control, such as relays activating fire doors or
machinery. Enter 1 if the end user will be restricted from accessing
this relay. Press
to continue.
43 = Communication failure
44 = RF low battery
45 = polling loop failure
51 = RF receiver failure
52 = kissoff
54 = fire zone reset
55 = disarm + 1 minute
56 = XX minutes (enter XX in field 1*74;
stop condition only)
57 = YY seconds (enter YY in field 1*75;
58 = Duress
60 = Audio/Video Alarm Verification
** Or at Disarming, whichever occurs earlier
The restore of all zone s on the Zone List will stop
to continue.
stop condition only)
to continue.
.
to continue.
– 105 –