Installation

WARNING! Back-to-back rack mounting of the
performed by factory-trained personnel only. Customers should not attempt to perform
this procedure.

Installation Strategy

The following general information and strategy applies to both the 1.6-meter and 2.0 meter racks. To
determine detailed components required for installation, refer to the "Installation Procedures" section later
in this appendix.
1. Upgrade the rack's power
The HP A4915A SureStore E Disk Array 12H Power Upgrade kit is supported only for 240 VAC
power systems. This upgrade provides three 10-receptacle 240 VAC PDUs. PDUs for non-US
installations must be ordered with the appropriate plugs, refer to the Table 20 below.
Table 20. A4915A Power Upgrade Kit, Power Options
PDU
A4915A
200-240 VAC North American PDU
Opt ABA
10 IEC-320 receptacles line cord is unterminated
A4915A
200-240 VAC International PDU
Opt ABB
10 IEC-320 receptacles line cord is unterminated
A4915A
200-240 VAC UPS PDU
Opt 024
10 IEC-320 receptacles 4.5M line cord is
unterminated
2. Upgrade the rack's cooling capacity
Back-to-Back racking requires that the cooling capacity of the rack be upgraded. The cooling upgrade
requires installation of a new Exhaust Fan Assembly (product E7687A). This assembly contains three
fans, an LED fault indication circuit and a 1- EIA unit air scoop. This is required to promote maximum
airflow through the center of the rack. Also, to promote additional air flow, the rear cabinet door will
be removed and set aside.
To maintain cooling efficiency, filler panels should be installed in any unfilled spaces in the front and
back of the rack (see Table 19).
HP AutoRAID Disk Array
Description
Appendix D. Back-to-Back Racking
Installation
should be
Use
US installations; PDUs
for High Availability
Non-US installations; PDUs for
High Availability
US or Non-US installations;
UPS PDUs for High availability