Appendix D. Back-to-Back Racking
Installation Procedure
5. Install Replacement PDU brackets
Install the PDU angle brackets supplied in the A4915A HP Power Upgrade Kit as described below (see
Figure
51):
a) Install the PDU brackets at the rear of the cabinet as described in the A4915A Upgrade Kit Quick
Installation Guide. However, when installing the brackets, two on the right column and two on the
left column, install them in the positions as indicated in the table below, not as described in the
quick installation guide.

Rack

1.6 Meter Rack -
2-meter
Rack -
NOTE -.Do not install the PDUs until after the disk array enclosures have been installed.
6. Install the disk enclosures
Replace any array enclosures you removed from the rack and install any new arrays. Refer to appendix C of
this document for array enclosure installation. Remember, when installing the disk modules, ensure that
they are installed back into the same enclosure from which they were removed.
NOTE! For optimum cooling efficiency, array enclosures should be racked from top to bottom in
the front of the rack and from bottom to top in the back of the rack. If side access to the rack is
not going to be possible, install the bottom and then the top array enclosure, leaving the array
position in the middle or top, open (middle for a 2-meter rack or top for a 1.6 meter rack).
246
Accessory Holes (as counted from the top of the
rack, down)
12 and 33
16 and 37