HP Surestore Disk Array 12h - And FC60 Service Manual page 175

Hp surestore e disk array 12h user's and service manual (c5445-90901, september 1999)
Hide thumbs Also See for Surestore Disk Array 12h - And FC60:
Table of Contents

Advertisement

Event
Event Name
Number
(DEC/hex)
Incompatible
195/0xc3
Address Table
In RAM Image
Non-Volatile
196/0xc4
SIMM Contents
Lost
Battery Failed
197/0xc5
Discharge Test
Event
Predictive
Logged
Maintenance
Implication
Y
Ignore -
Operator error
Ignore unless
Y
no operator
activity
Single
Y
Occurrence
Event Code Descriptions
Suspected
Description
Components
None
The controller has detected
that the amount of NVRAM
available for the address table
has been reduced. The disk
array uses all available
NVRAM to create the largest
possible address table, which
increases the total amount of
usable capacity the controller
can support. Once the size of
the address table has been
established, it cannot be
reduced.
This event is typically caused
by removing a SIMM from the
controller. Reinstall the SIMM
to correct the problem.
SIMM
This error occurs when
Controller
NVRAM has failed or has
been removed at a time when
its contents were critical to
disk array operation (not
shutdown). The NVRAM on
the affected controller is
invalidated due to missing
contents in the additional
NVRAM.
Batteries
A battery has failed the long
discharge test. This test occurs
following power on and every
30 days thereafter. The test
takes about 36 hours to
complete.
Replace both batteries.
Troubleshooting
175