Packaging Dimensions; Operating Characteristics And Requirements; Power Requirements; Airflow Space - HP Surestore Disk Array 12h - And FC60 Service Manual

Hp surestore e disk array 12h user's and service manual (c5445-90901, september 1999)
Hide thumbs Also See for Surestore Disk Array 12h - And FC60:
Table of Contents

Advertisement

Appendix A. Product Specifications

Operating Characteristics and Requirements

Packaging Dimensions

Packaging
Height
706 mm (27.8 in.)
Width
610 mm (24.0 in.)
Depth
508 mm (20.0 in.)
Operating Characteristics and Requirements

Power Requirements:

NOTE! Power requirements are specified for a unit during spin-up with a maximum configuration
of three fan modules, three power modules, twelve disk modules, and two controller modules.
870 W (7.3 A at 120 Vac, 3.8 A at 230 Vac)

Airflow Space

Minimum: 102 mm (4 in.) front and rear

Heat Dissipation

Minimum Configuration: 135 watts (460 Btu/hr; 115 kcals/hr)
Maximum Configuration: 750 watts (2560 Btu/hr; 645 kcals/hr)
Typical Configuration (with twelve 9.1-Gigabyte 7200 rpm disk modules in the enclosure): 420 watts
(1433 Btu/hr; 361 kcals/hr)