Absolute Encoder Setup
You must set up the absolute encoder if using a motor with an absolute encoder. The setup is
required when you turn ON the power supply for the first time, when an absolute encoder
system down error (alarm display No. 40) occurs, or when the encoder cable is disconnected
and then connected again.
When using an absolute encoder, set Pn015 to 0 or 2 and set Pn616 to 1.
Absolute Encoder Setup Procedure
1. Turn ON the power supply and align the origin position.
Turn ON the power supply, perform the origin adjustment operation, and move the machine to
the origin position.
2. Go to AUXILIARY FUNCTION mode.
Press
and
3. Use the Increment and Decrement keys to go to the ABSOLUTE ENCODER CLEAR
mode.
Press
again. ABSOLUTE ENCODER CLEAR mode will be displayed.
(AUXILIARY FUNCTION mode)
Mode selection
4. Start clearing the absolute encoder.
Hold down
OMNUC G5-SERIES AC SERVOMOTOR AND SERVO DRIVE USER'S MANUAL
ABS
on the driver. AUXILIARY FUNCTION mode will be displayed.
Alarm clear
A1 automatic offset
A2 automatic offset
A3 automatic offset
Motor trial operation
Absolute encoder clear
Parameter initialization
Front panel lock
. Clearing the absolute encoder will be started.
9-2 Preparing for Operation
Execute
9
9-4