4-4 Regenerative Energy Absorption

Connecting an External Regeneration Resistor

R88D-KTA5L/-KT01L/-KT02L/-KT01H/-KT02H/-KT04H
Normally B2 and B3 are open.
If an External Regeneration Resistor is necessary, remove the short-circuit bar between B2
and B3, and then connect the External Regeneration Resistor between B1 and B2 as shown
in the diagram below.
4
Connect the thermal switch output so that the main circuit power supply is shut OFF when the
contacts open.
When using multiple External Regeneration Resistors, connect each thermal switch in series.
The resistor may be damaged by burning, or cause fire if it is used without setting up a power
supply shutoff sequence using the output from the thermal switch.
R88D-KT04L/-KT08H/-KT10H/-KT15H/-KT20H/-KT30H/-KT50H/-KT06F/-
KT10F/-KT15F/-KT20F/-KT30F/-KT50F
Normally B2 and B3 are short-circuited.
If an External Regeneration Resistor is necessary, remove the short-circuit bar between B2
and B3, and then connect the External Regeneration Resistor between B1 and B2 as shown
in the diagram below.
Connect the thermal switch output so that the main circuit power supply is shut OFF when the
contacts open.
When using multiple External Regeneration Resistors, connect each thermal switch in series.
The resistor may be damaged by burning, or cause fire if it is used without setting up a power
supply shutoff sequence using the output from the thermal switch.
4-41
Servo Drive
θ >
B1
B3
B2
Precautions for Correct Use
Servo Drive
B1
B3
B2
Remove the short-circuit bar between B2 and B3.
Precautions for Correct Use
OMNUC G5-SERIES AC SERVOMOTOR AND SERVO DRIVE USER'S MANUAL
Thermal switch output
External Regeneration Resistor
θ >
Thermal switch output
External Regeneration Resistor