5-10 Clock Pulses

Overview
The Clock Pulses are turned ON and OFF by the CPU Unit's internal timer. These bits are specified
with symbols rather than addresses.
The CX-Programmer treats condition flags as system-defined symbols (global symbols) beginning with P_.
Notation
P_ 0_02s
Clock pulse name: 0_02s
I/O memory area designator:
P_ (indicates a system symbol name)
Details
The Clock Pulses are read-only; they cannot be written from instructions or from the CX-Programmer.
Clock Pulses
Name
0.02-s Clock Pulse
0.1-s clock pulse
0.2-s clock pulse
1-s clock pulse
1-min clock pulse
CP1E CPU Unit Software User's Manual(W480)
Name in CX-
Programmer
P_0_02s
P_0_1s
P_0_2s
P_1s
P_1min
Description
0.01s
0.01s
0.05s
0.05s
0.1s
0.1s
0.5s
0.5s
30s
30s
5 I/O Memory
5
ON for 0.01 s
OFF for 0.01 s
ON for 0.05 s
OFF for 0.05 s
ON for 0.1 s
OFF for 0.1 s
ON for 0.5 s
OFF for 0.5 s
ON for 30 s
OFF for 30 s