17-1-3 Specifications
Item
Name
Model number
Type
Applicable Programming Device
Unit classification
Mounting location
Size of Buffers
Transfer
Media access method CSMA/CD
Modulation method
Transmission paths
Baud rate
Transmission media
Transmission Dis-
tance
Number of cascade
connections
Weight
Dimensions
17-1-4 Software Configuration
The software supported by the Ethernet Option Board runs in the layers shown in the following diagram.
It is necessary to set the communications settings before connecting the Ethernet Option Board to the
CP1E CPU Unit by the Host Link protocol. Refer to Serial Communications Settings of the Option Board
in section 17-2-1.
FINS/UDP
UDP
CP1E CPU Unit Software User's Manual(W480)
CP-series Etherent Option Board
CP1W-CIF41
100Base-TX (Can be used as 10 Base-T )
CX-Programmer version 9.12 or higher
CP-series Option Board
One slot for a CP-series Option Board
8K bytes
Baseband
Star form
100 Mbit/s (100Base-TX)
However, the internal baud rate between the CPU Unit and the Ethernet
Option Board is 115.2 kbps.
• Unshielded twisted-pair (UDP)
cable
Categories: 5, 5e
• Shielded twisted-pair (STP) cable
Categories: 100Ω at 5, 5e
100 m (distance between hub and node)
No restrictions if switching hubs are used.
23 g max.
36.4×36.4×28.2 mm (W×H×D)
CP-series CPU Unit
Host Link
FINS Communication service
FINS
FINS/TCP
IP
ICMP
Ethernet (Ver.2.0)
17 Ethernet Option Board
Specifications
10 Mbit/s (10Base-T)
• Unshielded twisted-pair (UDP)
cable
Categories: 3, 4, 5, 5e
• Shielded twisted-pair (STP) cable
Categories: 100Ω at 3, 4, 5, 5e
CP1E CPU Unit
TCP
Ethernet Option Board
APR
17
17-5
Need help?
Do you have a question about the CP1E CPU UNIT SOFTWARE and is the answer not in the manual?
Questions and answers