Writing the Ladder Program
Reading A/D Conversion Values
Analog input device
Temperature sensor
Pressure sensor
Speed sensor
Flow sensor
Other device
Writing D/A Conversion Values
Ladder program
MOV instruction
MOV
Write conversion
value (SV).
Handling Unit Errors
When an error occurs in the built-in analog I/O system, analog input data will be set to 0000 and the
analog output will be set to 0 V or 0 mA.
If a CPU error occurs, the analog output will be set to is set to 0 V or 0 mA even if the output range is
1 to 5 V or 4 to 20 mA. For any other fatal errors in the CPU Unit, 1 V or 4 mA will be output if the
output range is 1 to 5 V or 4 to 20 mA.
CP1E CPU Unit Software User's Manual(W480)
Analog input 0 conversion value
Analog input 1 conversion value
CP1E NA-type CPU Unit
Analog output 1 SV
15 Analog I/O Function
CP1E NA-type CPU Unit
Ladder program
MOV
CIO 90
CIO 91
Analog output device
CIO 190
MOV instruction
Read conversion
value.
Adjustment equipment
Servo Controller
Inverter
Recorder
Other device
15-5
15