12 Pulse Outputs
Preparations
PLC Setup
Use define origin operation for pulse output 0.
Note The Use define origin operation setting is read from the PLC Setup when the power supply is turned ON.
DM Area Settings
• Settings for PLS2 for Fixed-distance Positioning (D0 to D7)
Acceleration rate: 1,000 Hz/4 ms
Deceleration rate: 1,000 Hz/4 ms
Target frequency: 50,000 Hz
Number of output pulses: 10,000 pulses
Starting frequency: 0 Hz
• Settings for PLS2 to Return to Start (D10 to D17)
Acceleration rate: 300 Hz/4 ms
Deceleration rate: 200 Hz/4 ms
Target frequency: 50,000 Hz
Number of output pulses: 0 pulse
Starting frequency: 100 Hz
• Number of Repeats of Fixed-distance Positioning Operation (D20)
Number of repeats of fixed-distance positioning
operation (number of PCBs in stocker)
12-36
Setting
Setting details
Setting details
Setting details
Address
Data
D0
#03E8
D1
#03E8
D2
#C350
D3
#0000
D4
#2710
D5
#0000
D6
#0000
D7
#0000
Address
Data
D10
#012C
D11
#00C8
D12
#C350
D13
#0000
D14
#0000
D15
#0000
D16
#0064
D17
#0000
Address
Data
D20
#000F