Appendices
Address
Name
Words
Bits
A283
00
PWM Output 0
Output In-progress
Flag
A294
Task Number when
Program Stopped
A295
08
Instruction Processing
Error Flag
09
Indirect DM BCD Error
Flag
A-58
Function
ON when pulses are being output from
PWM output 0.
• Cleared when operation starts or
stops.
OFF: Stopped
ON: Outputting pulses.
This word contains the task number of
the task that was being executed when
program execution was stopped
because of a program error.
Note A298 and A299 contain the pro-
gram address where program
execution was stopped.
This flag and the Error Flag (ER) will be
turned ON when an instruction pro-
cessing error has occurred and the
PLC Setup has been set to stop opera-
tion for an instruction error. CPU Unit
operation will stop and the ERR/ALM
indicator will light when this flag goes
ON.
Note The task number where the error
occurred will be stored in A294
and the program address will be
stored in A298 and A299.
This flag and the Access Error Flag
(AER) will be turned ON when an indi-
rect DM BCD error has occurred and
the PLC Setup has been set to stop
operation an indirect DM BCD error.
(This error occurs when the content of
an indirectly addressed DM word is not
BCD although BCD mode has been
selected.) CPU Unit operation will stop
and the ERR/ALM indicator will light
when this flag goes ON.
Note The task number where the error
occurred will be stored in A294
and the program address will be
stored in A298 and A299.
Status
after
Settings
mode
change
Cleared
Cyclic tasks: 0000
Cleared
Cleared
Interrupt tasks: 8000
to 800F (task 0 to 15)
ON: Error Flag ON
Cleared
Cleared
OFF: Error Flag OFF
ON: Not BCD
Cleared
Cleared
OFF: Normal
CP1E CPU Unit Software User's Manual(W480)
Related
Status at
Write
flags,
startup
timing
settings
Refreshed
when pulse
output starts or
stops.
When pro-
A298/
gram error
A299
occurs.
When pro-
A294,
gram error
A298/
occurs.
A299
PLC
Setup
(Opera-
tion when
instruc-
tion error
has
occurred)
When pro-
A294,
gram error
A298/
occurs.
A299
PLC
Setup
(Opera-
tion when
instruc-
tion error
has
occurred)