17 Ethernet Option Board
Error
ERR
Meaning
code
LED
03C3
---
FINS/UDP Packet
discarded
03C8
---
Socket Error
03D0
FLASH
System setup sum
value error
0601
LIT
Option Board error
0602
LIT
Option Board mem-
ory error
---
FLASH
Serial Option Port
Communications Set-
tings error
17-34
Detailed error code
1st byte
2nd byte
00
01 to FE
Node address
Arbitrary
Arbitrary
01: Read error
06: Error log
02: Write error
Correction
The automatic genera-
tion (static) method was
used as the IP address
conversion method, so
remote IP address infor-
mation in internal memory
could not be changed.
Resend the packet or the
destination node is not in
the network.
Reset the value of system
setup area, Restart CPU
Unit.
Restart the CPU Unit. If
the problem persists,
replace the Ethernet
Option Board.
Restart the CPU Unit. If
the problem persists,
replace the Ethernet
Option Board.
Set the PLC Settings on
the Serial Option Port Tab
as follows, and then turn
the power ON again.
Communications Settings
• Baud: 115200
• Format: 7, 2, E
• Mode: Host Link
CP1E CPU Unit Software User's Manual(W480)
EEPROM
---
---
Saved
Saved
Saved
(except
error log)
---