Operation and indication | Operation and indication object list
8.4

Operation and indication object list

Object no.
1
1-bit object for disabling manual operation on the device. The polarity can be con-
figured.
Object no.
2
1-bit object for manual operation status transmission. The object is "OFF" when
manual operation is deactivated (bus control). The object is "ON" when manual oper-
ation is activated. You can configure whether temporary or permanent manual oper-
ation will be indicated as status information or not.
Object no.
3
1-bit object to signal and activate the temporary status indication. This object is bid-
irectional and can firstly signal the status of the temporary status indication, and
secondly, activate the status display. If a temporary status indication has been activ-
ated by pressing the "Manual operation" button, the object transmits the value "ON".
If the object receives a telegram with the value "OFF" or "ON", the status LEDs indic-
ate the status of the outputs according to the display length. Manual operation is not
activated in this case.
The object is only visible if the temporary status indication is activated
Heating actuator 6-gang with controller | Order no. 2139 00 | 21393100
Function
Disabling
Function
Status
Function
Temporary status in-
dication
Name
Manual operation -
Input
Name
Manual operation -
Output
Name
Manual operation -
Input/Output
Type
DPT
Flag
1-bit
1,003
C, (R), W, -,
A
Type
DPT
Flag
1-bit
1,002
C, R, -, T, A
Type
DPT
Flag
1-bit
1,002
C, (R), W,
T, A