Valve outputs | Operating hours counter
Start value
The start value of the down-counter is set here.
*: With second counter
**: With hour counter
This parameter is only visible in the "Down-counter" counter type and then only if the
parameter "Preset value" is set to "via parameter".
Cycle time
This parameter defines the cycle time for the cyclical transmission. Setting the cycle
time hours, minutes and seconds.
Counting interval
The interval of the counter value is set here for automatic transmission. The current
meter reading is transmitted to the KNX after the interval configured here.
*: With second counter
**: With hour counter
This parameter is only visible if the parameter "Transmission behaviour" is set to "on
change by interval value".
9.11.2 Objects for operating hours counter
Object no.
112, 119,
126, 133,
140, 147
1-bit object for resetting the operating hours counter of a valve output ("1" = Restart,
"0" = No reaction).
Object no.
113, 120,
127, 134,
141, 148
4-byte object to transmit or read out the current counter level of the operating hours
counter of a valve output.
Value range: 0...2147483647 seconds
If the bus voltage should fail, the value of the communication object is not lost and is
actively transmitted to the bus after bus voltage return or an ETS programming oper-
ation. In the as-delivered state, the value is "0".
This object is only available with the second counter.
Heating actuator 6-gang with controller | Order no. 2139 00 | 21393100
Function
Operating hours
counter - Restart
Function
Operating hours
counter - Meter
reading - Status
0...2147483647*
0...65535**
0...23 h
0...15...59 min
0...59 s
0...3600...2147483647 s *
0...1...65535 h **
Name
VO x ... - Input
Name
VO x ... - Output
Type
DPT
Flag
1-bit
1,015
C, (R), W, -,
A
Type
DPT
Flag
4 bytes 13,100 C, (R), -, T,
A