Valve outputs | Command value status
Status value for input command value "Constant (1-byte) with pulse width modulation
(PWM)"...
State of operation "Normal operation" -> Status value = Most recently received
input command value (0...100%),
State of operation "Emergency operation" (0...100%)
-> Status value = Emergency operation command value (0...100%),
State of operation "Forced position" (0...100%)
-> Status value = Forced command value (0...100%),
State of operation "Valve rinsing" (0%, 100%)
-> Status value = Current command value in rinsing operation ("0%" when
valve closed, "100%" when valve opened),
State of operation "Service mode" (0%, 100%)
-> Status value = Service command value ("0%" when valve forcibly closed,
"100%" when valve forcibly opened),
State of operation "After device reset" (0...100%)
-> Status value = According to presetting by parameter "Behaviour after bus or
mains voltage return" or "Behaviour after ETS programming
operation" ("0" at 0%, "1" at 1...100%),
State of operation "Manual operation" (5...100%)
-> Status value = Manual operation mode command value (0% CLOSE,
5...100% OPEN),
State of operation "Valve voltage failure" (0%, 100%)
-> Status value = Command value according to valve direction of action (0%
when deenergised closed, 100% when deenergised opened),
State of operation "Short-circuit / overload" (0%, 100%)
-> Status value = Command value according to valve direction of action (0%
when deenergised closed, 100% when deenergised opened).
Status value for input command value "Constant (1-byte) command value limiting
value"...
State of operation "Normal operation"
-> Status value = According to evaluation of the input command value by limit-
ing value and hysteresis ("0" for command value < limiting value - hysteresis
or "1" for command value >= limiting value),
State of operation "Emergency operation" (0...100%)
-> Status value = Emergency operation command value ("0" at 0%,
"1" at 1...100%),
State of operation "Forced position" (0...100%)
-> Status value = Forced command value ("0" at 0%, "1" at 1...100%),
State of operation "Valve rinsing" (0%, 100%)
-> Status value = Current command value in rinsing operation ("0" when valve
closed, "1" when valve opened),
State of operation "Service mode" (0%, 100%)
-> Status value = Service command value ("0" when valve forcibly closed, "1"
when valve forcibly opened),
Heating actuator 6-gang with controller | Order no. 2139 00 | 21393100