Logic functions | Converter (1 bit -> 1 byte)
11.3
Converter (1 bit -> 1 byte)
The converter has a 1-bit input and a 1-byte output and also a disabling object. ON /
OFF telegrams can be converted to preconfigured values. The disabling object is
able to deactivate the converter.
The converter can react differently to input states. The parameter "Reaction at input
to" defines whether the converter responds to ON and OFF commands or alternat-
ively only processes ON or OFF telegrams.
A concrete 1-byte output value can be assigned to each 1-bit input status. The two
output values c an be configured anywhere in the range 0 ... 255 as required. The
data format of the converter output object is set to DPT 5.001 (0...100%).
The disabling object can be deactivated via the converter. A deactivated converter no
longer processes input states and consequently does not convert any new output val-
ues ( the last value is retained and transmitted cyclically, if necessary). At the end of a
disabling function, the converter is enabled again. The converter then waits for the
next telegram at the input.
The telegram polarity of the disabling object can be configured.
The transmission behaviour of the converter output can be configured.
Heating actuator 6-gang with controller | Order no. 2139 00 | 21393100
Image 45: Converter (1 bit -> 1 byte)
Page 223 of 257