Operation and indication | Operation and indication parameters
Function
This parameter defines the information contained in the status object. The object is
always "OFF" when manual operation is deactivated.
0 = inactive; 1 = manual operation active: The object is "ON" when manual operation
is active (temporary or permanent).
0 = inactive; 1 = permanent manual operation active: The object is only "ON" when
permanent manual operation is active.
This parameter is only visible if the status function is enabled.
At end of permanent manual operation
The behaviour of the actuator at the end of permanent manual operation depends on
this parameter. This parameter is only visible if manual operation is enabled.
no change: All telegrams received during active permanent manual operation for dir-
ect operation (switching, long-time/short-time, positioning, central, scenes, command
value telegrams) will be rejected. After the end of the permanent manual operation,
the current state of all outputs which was most recently active in manual operation
remains unchanged. If, however, a forced position, a disabling function, a safety
function or a sun protection function (independent of priority) has been activated via
the KNX before or during manual operation, the actuator executes these functions
with a higher priority for the outputs concerned.
Track outputs: During active permanent manual operation, all incoming telegrams
(blinds operation exception: short-time telegrams – step/stop) are internally tracked.
At the end of the manual operation, the outputs will be set to the tracked states or to
the positions last set before the permanent manual operation for Venetian blind out-
puts. The individual priorities of the functions with respect to one another are taken
into account here. Only the function with the greater priority is executed. Long time
operation is not tracked in Venetian blind operation if the corresponding Venetian
blind output is already in the appropriate end position.
This parameter is only visible if manual operation is enabled.
Bus control of individual outputs can be
disabled
Individual outputs can be disabled locally during permanent manual operation, so
that the disabled outputs can no longer be controlled via the KNX. Disabling via
manual operation is only permitted if this parameter is activated.
This parameter is only visible if manual operation is enabled.
Status indication
Heating actuator 6-gang with controller | Order no. 2139 00 | 21393100
0 = inactive; 1 = manual operation active
0 = inactive; 1 = permanent manual oper-
ation active
no change
Output tracking
Checkbox (yes / no)