Valve outputs | Command value status
If the supply voltage of the actuators fails and returns, then the status mes-
sage is always transmitted without a delay, providing that the bus voltage sup-
ply is switched on.
Setting cyclical transmission of the command value status message
The status message telegram can also be transmitted cyclically via the object in addi-
tion to the transmission after changes.
Set the parameter "Transmit on" to "change and cyclical".
Cyclical transmission is activated.
Set the parameter "Transmit on" to "change".
Cyclical transmission is deactivated so that the status is transmitted to the bus
only when changed by the actuator.
The cycle time is defined centrally for all the valve outputs on the parameter
page "General".
There is no cyclical transmission during an active time delay after bus voltage
return or an ETS programming operation.

9.8.1 Status parameters

Valve output x - General -> Enabled functions
Status
This parameter generally enables the feedback functions.
The feedback functions are configured on the "Status" parameter page.
Valve output x - General -> Status
Valve command value
This parameter enables the status object "Command value - Status". The data point
type corresponds to the input object "Command value"
The status object makes the active command value of the valve output available. All
functions are taken into account that have an influence on the command value im-
plemented at the output.
Heating actuator 6-gang with controller | Order no. 2139 00 | 21393100
Checkbox (yes / no)
Active
Inactive