Heating actuator 6-gang with controller
Table of Contents

Advertisement

Room temperature controller | Scenes
Presetting scene numbers and scene operating modes
The presetting of the scene number can be defined for each scene of the room tem-
perature controller, by which scene number (1...64) the scene is addressed, i.e.
called up or stored.
The data point type of the scene extension object permits addressing of up to 64
scenes max.
In addition to defining the scene number, it must be defined which scene command
(Comfort mode, Standby mode, Night mode, Frost/heat protection) is to be set when
a scene is called up on the room temperature controller.
Precondition
The scene function must be enabled on the parameter page "Room temperature con-
troller x -> RTCx - General -> Enabled functions".
On the parameter page "Room temperature controller x -> RTCx - General ->
Scenes", set the parameter "Scene number" for each scene to the number by
which the scenes are to be addressed.
A scene can be addressed with the configured scene number. A setting of "0"
deactivates the corresponding scene so that neither recalling nor storage is
possible.
If the same scene number is configured for several scenes, only the scene
with the lowest sequential number will be addressed. The other scenes will be
ignored in this case.
On the parameter page "Room temperature controller RTC -> RTC - General -
> Scenes", set the "Operating mode" parameter for each scene to the desired
operating mode.
With a scene recall, the configured operating mode is recalled and set at the
room temperature controller.
The configured operating mode is adopted in the actuator during an ETS pro-
gramming operation only if the parameter "Overwrite values stored in the
device during the ETS programming operation" is activated.
Presetting storage behaviour
The operating mode set on the room temperature controller can be stored internally
when a scene storage telegram is received via the extension object. The operating
mode can be influenced by all functions of the room temperature controller before
storage, provided that the individual functions are also enabled.
Precondition
The scene function must be enabled on the parameter page "Room temperature con-
troller x -> RTCx - General -> Enabled functions".
On the parameter page "Room temperature controller x -> RTCx - General ->
Scenes", activate the "Storage function" parameter for each scene.