Objects For Operating Mode And Setpoints - Gira KNX 2139 00 Product Documentation

Heating actuator 6-gang with controller
Table of Contents

Advertisement

Room temperature controller | Operating mode and setpoints
Setpoint temperature transmission behaviour
on change by
Determines the size of the value change required to transmit the current value auto-
matically to the bus via the "Setpoint temperature" object. In the "0" setting, the set-
point temperature is not transmitted automatically when there is a change.
Cyclical (0 = inactive)
This parameter determines whether the setpoint temperature is to be transmitted
cyclically via the "Setpoint temperature" object. Definition of the cycle time by this
parameter. In the "0" setting, the setpoint temperature is not transmitted cyclically.

10.3.2 Objects for operating mode and setpoints

Object no.
334, 384,
434, 484,
534, 584,
634, 684,
734, 784,
834, 884
1-byte object for change-over of the operating mode of the controller according to
the KNX specification.
After voltage return or an ETS programming operation, the current operating mode is
transmitted via this object.
Object no.
335, 385,
435, 485,
535, 585,
635, 685,
735, 785,
835, 885
1-byte object for forced change-over (highest priority) of the operating mode of the
controller according to the KNX specification.
Heating actuator 6-gang with controller | Order no. 2139 00 | 21393100
Function
Operating mode -
Preset
Function
Operating mode -
Forced
0...0.1...25.5 K
0...255 min
Name
RTC x - Input
Name
RTC x - Input
Type
DPT
Flag
1 bytes 20,102 C, -, W, T, -
Type
DPT
Flag
1 bytes 20,102 C, -, W, T,
U
Page 159 of 257