Operation and indication | ETS configuration
During active permanent manual operation, all incoming telegrams are tracked
internally. At the end of manual operation, the outputs will be set to the tracked
states or to the positions last set before the permanent manual operation. The
individual priorities of the functions with respect to one another are taken into
account here. Only the function with the greater priority is executed.
The operations triggered during manual operation update the states of the
feedback and status objects. Telegrams are also transmitted to the KNX, if the
signal objects concerned are enabled in the ETS and are configured as act-
ively transmitting.
During an ETS programming operation, an activated manual operation mode
will always be terminated. In this case, the parameterised or predefined beha-
viour at the end of manual operation will not be executed. The actuator ex-
ecutes the configured behaviour after ETS programming instead.
Presetting the status message function for manual operation
An actuator can transmit a status telegram to the KNX via a separate object when the
manual operation is activated or deactivated. The status telegram can only be trans-
mitted when the bus voltage is switched on. The polarity of the status telegram can
be parameterised.
Manual operation must be enabled.
Activate the parameter "Status object" on the "Manual operation" parameter
page.
The status messaging function of manual operation is enabled and the status
object is visible.
Specify in the parameter "Function" whether the status telegram is generally
an "ON" telegram whenever manual operation is activated or only in those
cases where permanent manual operation is activated.
The status object is always "OFF" when the manual operation is deactivated.
The "inactive" status is transmitted automatically to the bus after bus voltage
return or an ETS programming operation.
When active manual operation is terminated by a disable, the actuator will also
transmit a "Manual operation inactive" status telegram to the bus.
Setting disabling of the bus control
Individual outputs can be disabled locally by manual operation on the device so that
the connected valves can no longer be controlled via the KNX. Such disabling of the
bus operation is initiated by operation in permanent manual operation mode and is
indicated by rapid flashing of the status LEDs on the front panel of the device. The
disabled outputs can then only be activated in permanent manual operation.
Manual operation must be enabled.
Heating actuator 6-gang with controller | Order no. 2139 00 | 21393100