1Scene Parameters - Gira KNX 2139 00 Product Documentation

Heating actuator 6-gang with controller
Table of Contents

Advertisement

Room temperature controller | Scenes
A scene overflow is not possible. After reaching the last scene of the selected
configuration, further ON telegrams of the extended scene recall are ignored.
In the same way, the actuator ignores further OFF telegrams if scene 1 was
recalled last.
10.11.1
Scene parameters
Room temperature controller RTC -> RTC - General -> Enabled functions
Scenes
This parameter can be used disable or to enable the scene function.
Room temperature controller RTC -> RTC - General -> Scenes
Delay scene recall
A scene is recalled via the scene extension object. If required, the scene recall can
be delayed on reception of a recall telegram (parameter activated). The recall is al-
ternatively made immediately on reception of the telegram (parameter deactivated).
Delay time minutes (0...59)
This parameter specifies the length of the scene delay time. Sets the scene delay
time in minutes.
Seconds (0...59)
Sets the scene delay time in seconds.
The delay time parameters are only visible, if the parameter "Delay scene recall" is
activated.
Overwrite values stored in the device dur-
ing the ETS programming operation
During storage of a scene, the scene values are stored internally to memory in the
device. To prevent the stored values from being replaced during ETS programming
by the originally programmed scene values, the actuator can inhibit overwriting of
the scene values (parameter deactivated). As an alternative, the original values can
be reloaded into the device during each programming run of the ETS (parameter ac-
tivated).
Extended scene recall
The extended scene recall allows calling of up to 64 scenes of a controller in se-
quence. Here, scene recall takes place via the 1-bit communication object "Extended
scene recall". Each ON telegram received via this object recalls the next scene.
Each OFF telegram received recalls the previous scene.
This parameter enables extended scene recall, if required.
Heating actuator 6-gang with controller | Order no. 2139 00 | 21393100
Checkbox (yes / no)
Checkbox (yes / no)
0...59
0...10...59
Checkbox (yes / no)
Checkbox (yes / no)
Page 210 of 257