Gira KNX 2139 00 Product Documentation page 152

Heating actuator 6-gang with controller
Table of Contents

Advertisement

Room temperature controller | Operating mode and setpoints
T
Comfort setpoint add. level Heating
add. level Cooling
T
Standby setpoint add. level Heating
point add. level Cooling
T
Standby setpoint heating
or
T
Comfort setpoint add. level Heating
point add. level Cooling
T
Night setpoint add. level Heating
Cooling
T
Night setpoint heating
In the case of switching 2-point feedback control, the hysteresis values must
additionally be taken into account.
Deadband and deadband positions in the combined heating and cooling operating
mode
With relative setpoint presetting, the comfort setpoint temperatures for heating and
cooling are derived from the basic setpoint in consideration of the set deadband. The
deadband (temperature zone for which there is neither heating nor cooling) is the dif-
ference between the comfort setpoint temperatures. This deadband does not exist for
absolute setpoint presetting.
The parameters "Deadband between heating and cooling", "Allocation of deadband"
and "Basic setpoint temperature" are specified in the ETS configuration. One distin-
guishes between the following settings...
Allocation of deadband = "symmetrical"
The deadband preset in the ETS is divided into two parts at the basic setpoint.
Based on the resulting half deadband, the comfort setpoint temperatures are
derived directly from the basic setpoint.
The following applies...
T
Basic setpoint
and
T
Basic setpoint
-> T
Comfort setpoint cooling
-> T
Comfort setpoint cooling
Allocation of deadband = "asymmetrical"
With this setting the comfort setpoint temperature for heating equals the basic
setpoint. The deadband preset in the ETS is effective only from the basic set-
point in the direction of comfort temperature for cooling. Thus the comfort set-
temperature for cooling is derived directly from the comfort setpoint for heat-
ing.
The following applies...
T
Basic setpoint
-> T
Basic setpoint
-> T
Comfort setpoint cooling
-> T
Comfort setpoint cooling
Heating actuator 6-gang with controller | Order no. 2139 00 | 21393100
≤ T
Comfort setpoint basic level Heating
≤ T
Standby setpoint basic level Heating
≤ T
Comfort setpoint heating
≤ T
Comfort setpoint basic level Heating
≤ T
Night setpoint basic level Heating
≤ T
≤ T
Comfort setpoint heating
– ½T
= T
Deadband
Comfort setpoint heating
+ ½T
= T
Deadband
Comfort setpoint cooling
– T
Comfort setpoint heating
≥ T
Comfort setpoint heating
= T
Comfort setpoint heating
+ T
= T
Deadband
Comfort setpoint cooling
– T
Comfort setpoint heating
≥ T
Comfort setpoint heating
≤ T
Comfort setpoint basic level Cooling
≤ T
Standby setpoint basic level Cooling
≤ T
≤ T
Comfort setpoint cooling
≤ T
Comfort setpoint basic level Cooling
≤ T
Night setpoint basic level Cooling
≤ T
Comfort setpoint cooling
= T
Deadband
= T
Deadband
≤ T
≤ T
Standby setpoint cooling
≤ T
≤ T
Night setpoint add. level
Night setpoint cooling
Page 152 of 257