Gira KNX 2139 00 Product Documentation page 251

Heating actuator 6-gang with controller
Table of Contents

Advertisement

Logic functions | Limit value switch
Upper threshold value (H2)
(-32768...32767)
This parameter defines the upper threshold value (H2) of the limit value switch.
This parameter is only available if the "data format" is set to "2 byte value
-32768...32767 (DPT 8.001)".
Upper threshold value (H2)
(-671088...670760)
This parameter defines the upper threshold value (H2) of the limit value switch.
This parameter is only available if the "data format" is set to "2 byte floating point
value (DPT 9.0xx)".
Upper threshold value (H2)
(-2147483648...2147483647)
This parameter defines the upper threshold value (H2) of the limit value switch.
This parameter is only available if the "data format" is set to "4 byte value
-2147483648...2147483647 (DPT 13.001)".
Telegram on reaching or exceeding the
upper threshold value
The telegram of the output upon reaching or exceeding the upper threshold can be
configured here.
Telegram on falling below the lower
threshold value
The telegram of the output upon not reaching the lower threshold can be configured
here.
Transmission criteria
The transmission behaviour of the output can be configured here.
Always transmit when the input is updated: The output transmits the current object
value to the KNX with every telegram that is received at the input.
Transmit only if the output changes: The output only transmits the current object
value if the object value has changed compared to the last transmission process.
During the first telegram to an input after bus voltage return or after an ETS pro-
gramming operation, the output always transmits to an input.
Transmit cyclically: With this setting, the output transmits the current object value to
the KNX cyclically. After bus voltage return or after an ETS programming operation,
the cyclical transmission is only started once the first telegram has been received at
the input. The output also transmits as soon as a new telegram is received at the in-
put. At the same time, the cycle time for cyclical transmission is restarted!
Heating actuator 6-gang with controller | Order no. 2139 00 | 21393100
-32768...0...32767
-671088...0...670760
-2147483648...0...2147483647
ON telegram
OFF telegram
ON telegram
OFF telegram
always transmit when the input is updated
transmit only if the output changes
transmit cyclically
Page 251 of 257