Gira KNX 2139 00 Product Documentation page 177

Heating actuator 6-gang with controller
Table of Contents

Advertisement

Room temperature controller | Command value output and command
value limit
Object no.
936, 978,
1020, 1062,
1104, 1146,
1188, 1230,
1272, 1314,
1356, 1398
1-bit object to output the combined switching command value for additional level in
two-level operation. This object is only available in this way if the command values
for heating and cooling mode are output to a shared object (parameter-dependent).
The type of feedback control must also be configured to "Switching 2-point feedback
control".
Object for command value output, cooling
Function: Command value
Object no.
937, 979,
1021, 1063,
1105, 1147,
1189, 1231,
1273, 1315,
1357, 1399
968, 1010,
1052, 1094,
1136, 1178,
1262, 1304,
1346, 1388,
1430 *
1-byte object to output the continuous command value of the cooling mode. In two-
level cooling mode, command value output for the basic cooling. This object is only
available in this way if the type of feedback control is configured to "Continuous PI
control".
* These objects are only visible if, with combined heating/cooling command value,
separate command value objects are also displayed.
Function: Command value
Heating actuator 6-gang with controller | Order no. 2139 00 | 21393100
Function
Command value -
Additional level
heating/cooling
Function
Command value -
Cooling / Command
value basic level
cooling
Command value -
Cooling / Command
value basic level
cooling
Name
RTC x - Output
Name
RTC x - Output
RTC x - Output
Type
DPT
Flag
1-bit
1,001
C, (R), -, T,
-
Type
DPT
Flag
1 bytes 5,001
C, (R), -, T,
-
1 bytes 5,001
C, (R), -, T,
-
Page 177 of 257