Room temperature controller | Command value output and command
value limit
Additional level heating
At this point, it is possible to specify whether the command value telegram for the
additional level heating is output normally or in inverted form.
This parameter is only visible if the operating mode "Heating" or "Heating and cool-
ing" is configured along with two-level operation.
Cooling
At this point, it is possible to specify whether the command value telegram for cool-
ing is output normally or in inverted form.
This parameter is only visible if the operating mode "Cooling" or "Heating and cool-
ing" is configured and not two-level operation.
Basic level cooling
At this point, it is possible to specify whether the command value telegram for the
basic level cooling is output normally or in inverted form.
This parameter is only visible if the operating mode "Cooling" or "Heating and cool-
ing" is configured along with two-level operation.
Additional level cooling
At this point, it is possible to specify whether the command value telegram for the
additional level cooling is output normally or in inverted form.
This parameter is only visible if the operating mode "Cooling" or "Heating and cool-
ing" is configured along with two-level operation.
Transmission behaviour
On change by (0 = inactive)
This parameter determines the size of the command value change that will automat-
ically transmit continuous command value telegrams via the command value objects.
Thus this parameter only affects command values which are configured to "Continu-
ous PI control" and to the 1 byte additional command value objects of the "Switching
PI control (PWM)".
Heating actuator 6-gang with controller | Order no. 2139 00 | 21393100
normal (under current, this means
opened)
inverted (under current, this means
closed)
normal (under current, this means
opened)
inverted (under current, this means
closed)
normal (under current, this means
opened)
inverted (under current, this means
closed)
normal (under current, this means
opened)
inverted (under current, this means
closed)
0...3...100 %