Gira KNX 2139 00 Product Documentation page 129

Heating actuator 6-gang with controller
Table of Contents

Advertisement

Room temperature controller | Room temperature controller - General
Type of heating Proportional
Heat water
heating
Underfloor
heating
Electrical heat-
ing
Fan
coil unit
Split unit (split
climate control
unit)
Predefined control parameters and recommend control types for heating systems
Cooling type
Cooling ceiling
Fan
coil unit
Split unit (split
climate control
unit)
Underfloor
cooling
Predefined control parameters and recommend control types for cooling systems
If the "Type of heating" or "Type of cooling" parameters are set to "Via control para-
meters", it is possible to adjust the control parameters manually. The feedback con-
trol may be considerably influenced by presetting the proportional range for heating
or for cooling (P component) and the reset time for heating or for cooling (I compon-
ent).
Even small adjustments of the control parameters will lead to noticeable differ-
ent control behaviour.
The adaptation should start with the control parameter setting for the corres-
ponding heating or cooling system according to the specified fixed values
mentioned in the above tables.
Heating actuator 6-gang with controller | Order no. 2139 00 | 21393100
Reset time
range (preset)
(preset)
1 Kelvin
830 minutes
1.5 Kelvin
1000 minutes
1 Kelvin
830 minutes
1 Kelvin
500 minutes
1 Kelvin
500 minutes
Proportional
Reset time
range (preset)
(preset)
1 Kelvin
830 minutes
1 Kelvin
500 minutes
1 Kelvin
500 minutes
1.5 Kelvin
1000 minutes
Recommended
Recommended
PI control type
PWM cycle time
Continuous /
15 min.
PWM
PWM
15-20 min.
PWM
10-15 min.
Continuous
---
PWM
10-15 min.
Recommended
Recommended
PI control type
PWM cycle time
PWM
15-20 min.
Continuous
---
PWM
10-15 min.
PWM
15-20 min.
Page 129 of 257