Logic functions | Limit value switch
Transmission delay for sending the hours
result (0...99)
An optional delay before result transmission (telegram at output) can be configured.
With the setting "always transmit when the input is updated": Telegrams at the out-
put are only transmitted after the trigger when the delay has elapsed. The delay time
is restarted by each telegram at the input.
With the setting "only transmit if the output changes": Telegrams are only sent when
the object value changes at the output if the delay has expired. If the logic function is
reprocessed by a new telegram at the input within the delay time and the object
value changes again, then the delay restarts. If the object value of the output does
not change due to new input telegrams, the delay does not restart.
This parameter defines the hours of the delay time.
Minutes (0...59)
This parameter defines the minutes of the delay time.
Seconds (0...59)
This parameter defines the seconds of the delay time.
The parameters for the transmission delay are only visible for "Transmission criteria"
= "Always transmit when the input is updated" and "Only transmit when the output
changes".
Cycle time hours (0...99)
During cyclical transmission of the output, this parameter defines the cycle time.
Setting the cycle time hours.
Minutes (0...59)
This parameter defines the minutes of the cycle time.
Seconds (0...59)
This parameter defines the seconds of the cycle time.
The parameters for the cycle time are only visible if "transmission criteria" = "transmit
cyclically".
Heating actuator 6-gang with controller | Order no. 2139 00 | 21393100
0...99
0...59
0...59
0...99
0...5...59
0...59
Page 252 of 257