Heating actuator 6-gang with controller
4
Operation
(3)
Status LEDs for outputs
(7)
Button ǃ – Manual operation
LED - On: permanent manual operation mode active
(8)
Open button – Open valve
LED – On: valve opened, manual operation mode
(9)
Close button – Close valve
LED – On: valve closed, manual operation mode
(10)
ALL OP / CL button – Central operating function for all outputs in case of
permanent manual operation: Open and close all valves alternately
Status display and output behaviour
The status LEDs A1...A6 (3) show whether the current flow is switched on or
switched off at the appropriate output. The connected heating or cooling valves open
and close according to their characteristics.
Valve drive
Deenergised closed
Deenergised opened
–
Status LED flashes slowly: output in manual operation mode
–
Status LED flashes quickly: output disabled via permanent manual operation
mode
Operating modes
–
Bus operation: operation via push-button sensors, for example
–
Temporary manual operation mode: manual operation on device with button
field, automatic return to bus mode
–
Permanent manual operation mode: exclusively manual operation on the
device
No bus operation is possible in manual operation mode.
All controlled valve outputs switch off after bus voltage failure.
82406412
Image 2: Operating elements
Status LED on
Heating/cooling
Valve opened
Valve closed
29.08.2022
Status LED off
Valve closed
Heating/cooling
Valve opened
7 / 17