Command Value Limit Parameters - Gira KNX 2139 00 Product Documentation

Heating actuator 6-gang with controller
Table of Contents

Advertisement

Valve outputs | Command value limit
In this setting, the actuator activates the command value limit automatically
after an ETS programming operation. To deactivate the limit a "0" telegram
must be received via the "Command value limit" object. The limit can be
switched on or off at any time using the object.
The status of the command value limit is not automatically tracked in the com-
munication object after a device reset.
It is to be noted that, on account of priority control, the actuator executes the
behaviour configured by the parameters "Behaviour after bus voltage return"
and "Behaviour after an ETS programming operation" on the parameter page
"VOx - General" after bus voltage return and an ETS programming operation.
The command values preset via configuration after a device reset are not influ-
enced by a command value limit. A command value limit only influences the
input command values preset via the bus or emergency operation command
values during command value monitoring.

9.6.1 Command value limit parameters

Enabling the function "Command value limit"
VOx - General -> Enabled functions
Command value limit
This parameter enables the command value limit. The command value range is
defined by a configurable smallest and a configurable largest command value.
Setting the function "Command value limit"
VOx - General -> Command value limit
Activation
This parameter decides whether the limit of the command values can either be activ-
ated and deactivated by the "Command value limit" object or whether the command
value limit is permanently active.
Active after bus voltage return
This parameter decides whether the command value limit is activated or inactive
after voltage return.
Active after ETS programming operation
This parameter decides whether the command value limit is activated or inactive
after an ETS programming operation.
Minimum command value
The minimum command value that is valid when the command value limit is activ-
ated is defined here.
Heating actuator 6-gang with controller | Order no. 2139 00 | 21393100
Checkbox (yes / no)
via object
permanently active
Checkbox (yes / no)
Checkbox (yes / no)
0 ... 50%
Page 87 of 257