Objects For Command Value Output And Command Value Limit - Gira KNX 2139 00 Product Documentation

Heating actuator 6-gang with controller
Table of Contents

Advertisement

Room temperature controller | Command value output and command
value limit
Cooling (also for basic level or additional level)
Minimum command value
The "Minimum command value" parameter specifies the lower command value limit-
ing value for cooling. With an active command value limit, the set minimum com-
mand value is not undershot by command values. If the controller calculates smaller
command values, it sets the configured minimum command value. The controller
transmits a 0% command value if no more heating or cooling energy has to be de-
manded.
Maximum command value
The "Maximum command value" parameter specifies the upper command value lim-
iting value for cooling. With an active command value limit, the set maximum com-
mand value is not exceeded. If the controller calculates larger command values, it
sets the configured maximum command value.

10.4.3 Objects for command value output and command value limit

Object for heating command value output and combined valve heating/cooling
Function: Command value
Object no.
935, 977,
1019, 1061,
1103, 1145,
1187, 1229,
1271, 1313,
1355, 1397
966, 1008,
1050, 1092,
1134, 1176,
1218, 1260,
1302, 1344,
1386, 1428
*
1-byte object to output the continuous command value of the heating mode. In two-
level heating mode, command value output for the basic heating. This object is only
available in this way if the type of feedback control is configured to "Continuous PI
control".
* These objects are only visible if, with combined heating/cooling command value,
separate command value objects are also displayed.
Function: Command value
Heating actuator 6-gang with controller | Order no. 2139 00 | 21393100
Function
Command value -
Heating / Command
value basic level
heating
Command value -
Heating / Command
value basic level
heating
5%, 10%, 15%, 20%, 25%, 30%, 35%,
40%, 45%, 50%
55%, 60%, 65%, 70%, 75%, 80%, 85%,
90%, 95%, 100%
Name
RTC x - Output
RTC x - Output
Type
DPT
Flag
1 bytes 5,001
C, (R), -, T,
-
1 bytes 5,001
C, (R), -, T,
-