Objects For "Valve Output - General - Gira KNX 2139 00 Product Documentation

Heating actuator 6-gang with controller
Table of Contents

Advertisement

Valve outputs | Valve output - General
Command value
The command value to be set after an ETS programming operation is defined here.
This parameter is only visible on "Behaviour after ETS programming operation" =
"Preset command value".
For valve outputs configured in the ETS to the command value data formats "Switch-
ing (1-bit)" or "Constant (1-byte) with command value limiting value", a constant
command value can also be preset using this parameter. In this case, a pulse width
modulation (5% ... 95%) is executed for the affected command value outputs. In the
"0%" and "100%" presettings, the valve outputs are activated continuously. The pre-
set PWM remains active until other functions have been executed or a new com-
mand value telegram is received via the bus, overriding the constant command
value on the valve output.

9.4.7 Objects for "Valve output - General"

Function command value presetting
Object no.
20, 35, 50,
65, 80, 96
1-bit input object for the presetting of a switching command value, e.g. of a KNX
room temperature controller. In this case, the telegram polarity is fixed: "0" = Close
valve, "1" = Open valve. The configured valve direction of action is taken into ac-
count in the electrical activation of the valve.
This object is only available for valve outputs configured in the ETS to the command
value data format "Switching (1-bit)".
Function command value presetting
Heating actuator 6-gang with controller | Order no. 2139 00 | 21393100
Function
Command value
0 %
5 %
10 %
...
90 %
95 %
100 %
Name
VOx - Input (x =
1...6)
Type
DPT
Flag
1-bit
1,001
C, (R), W, -,
-
Page 80 of 257