Gira KNX 2139 00 Product Documentation page 156

Heating actuator 6-gang with controller
Table of Contents

Advertisement

Room temperature controller | Operating mode and setpoints
Night mode
The value by which the night temperature for cooling is raised compared to the cool-
ing comfort temperature.
The parameter is only visible in the "Heating" or "Heating and cooling" operating
mode (if necessary with additional levels) and only with relative setpoint presetting.
Heat protection
This parameter specifies the setpoint temperature for heat protection. The parameter
is only visible in "Cooling" or "Heating and cooling" operating modes (if necessary
with additional levels).
Difference between basic and additional
levels
In a two stage control mode it is necessary to determine the temperature difference
to the basic stage with which the additional stage is to be incorporated into the con-
trol. This parameter defines the level spacing.
The parameter can only be seen in two-level control operation.
Setpoint temperature shift
Maximum shift upwards
This is used to define the maximum range in which the basic setpoint temperature
can be adjusted upwards.
This parameter is only visible with relative setpoint presetting!
Heating actuator 6-gang with controller | Order no. 2139 00 | 21393100
0...4...10 K
7 ... 35.0 ... 45 °C
0...2...12.7 K
0 K
+ 1 K
+ 2 K
+ 3 K
+ 4 K
+ 5 K
+ 6 K
+ 7 K
+ 8 K
+ 9 K
+ 10 K
Page 156 of 257