2Objects For Setpoint Temperature Increase; Scenes - Gira KNX 2139 00 Product Documentation

Heating actuator 6-gang with controller
Table of Contents

Advertisement

Room temperature controller | Scenes
10.10.2
Objects for setpoint temperature increase
Object no.
363, 413,
463, 513,
563, 613,
663, 713,
763, 813,
863, 913
1-bit object for signalling an active setpoint temperature increase.
"0" = raising of setpoint not active
"1" = raising of setpoint active

10.11 Scenes

Up to 64 scenes can be created for the room temperature controller and scene val-
ues (operating mode) stored. The scene values are recalled or stored via a separate
scene extension object. The data point type of the extension object permits address-
ing of all scenes.
The scene function must be enabled on the parameter page "Room temperature con-
troller -> RTCx - General -> Enabled functions" so that the required communication
objects and parameters (on the parameter page "Room temperature controller ->
RTCx - General -> Scenes") become visible.
The scene configuration selected in the parameterization decides whether the num-
ber of scenes is either variable (1 ... 64) or alternatively fixed to the maximum (64).
Scene configuration = "variable (1 ... 64 scenes)"
With this setting, the number of scenes used can be selected anywhere in the
range 1 to 64. The parameter "Number of scenes" decides how many scenes
are visible in the ETS and can therefore be used. It is possible to specify which
scene number (1 ... 64) controls each scene.
Scene configuration = "fixed (64 scenes)"
With this setting, all scenes are always visible and can therefore be used. The
scenes are controlled via permanently assigned scene numbers (1 ... 64)
(scene number 1 -> scene 1, scene number 2 -> scene 2 ...). If necessary, in-
dividual scenes can be deactivated.
The scene function can be combined together with other functions of the room tem-
perature controller, whereby the last received or set state is always executed.
Presetting a scene recall delay
Each scene recall of the room temperature controller can also be optionally delayed.
With this feature, dynamic scene sequences can be configured if several scene out-
puts are combined with cyclical scene telegrams.
Heating actuator 6-gang with controller | Order no. 2139 00 | 21393100
Function
Setpoint temperat-
ure increase -
Status
Name
RTC x - Output
Type
DPT
Flag
1-bit
1,011
C, R, -, T, A
Page 206 of 257