Room temperature controller | Room temperature controller - General

10.2.5 Reset behaviour

Additional information on the operating mode after a reset
In the ETS, it is possible to use the parameter "Operating mode after reset" in the
parameter node "Room temperature controller -> RTCx - General" to set which oper-
ating mode is to be activated after bus voltage returns or after an ETS programming
operation. The following settings are possible here...
"Comfort" -> The Comfort mode will be activated after the initialisation phase.
"Standby" -> The standby mode will be activated after the initialisation phase.
"Night" -> The Night mode will be activated after the initialisation phase.
"Frost/heat protection" -> The frost/heat protection mode will be activated after
the initialisation phase.
"Restore operating mode before reset" -> The mode set before a reset accord-
ing to the operating mode objects will be restored after the initialisation phase
of the device. Operating modes set by a function with a higher priority before
the reset (Forced, Window status, Presence status) are not effected.

10.2.6 "Room temperature controller - General" parameters

Name of the controller
The text entered in this parameter is used to label the controller in the ETS para-
meter window (e.g. "Kitchen control", "Bathroom temperature"). The text is not pro-
grammed in the device.
Operating mode
The room temperature controller distinguishes between two different operating
modes. The operating modes specify whether you want the controller to use its com-
mand value to trigger heating systems ("heating" single operating mode) or cooling
systems ("cooling" single operating mode). You can also activate mixed operation,
with the controller being capable of changing over between "Heating" and "Cooling"
either automatically or, alternatively, controlled by a communication object.
In addition, you can establish two-level control operation to control an additional
heating or cooling unit. For two-level feedback control, separate command values
will be calculated as a function of the temperature deviation between the setpoint
and the actual value and transmitted to the bus for the basic and additional levels.
This parameter specifies the operating mode and, if necessary, enables the addi-
tional level(s).
Heating actuator 6-gang with controller | Order no. 2139 00 | 21393100
40-character free text
Heating
Cooling
Heating and cooling
Basic and additional heating
Basic and additional cooling
Basic and additional heating and cooling
Page 135 of 257