Gira KNX 2139 00 Product Documentation page 228

Heating actuator 6-gang with controller
Table of Contents

Advertisement

Logic functions | Disabling element [Filtering/Time]
Filter function
ON -> ON / OFF -> ---
ON -> OFF / OFF -> ON
ON -> --- / OFF -> ON
ON -> OFF / OFF -> ---
The disabling element can be deactivated by the disabling object. A deactivated dis-
abling element no longer forwards any input states to the filter and consequently
does not convert any new output values ​ ​ ( the last value is retained and transmitted
cyclically, if necessary). However, the input states are still evaluated (even with ef-
fective delays). At the end of a disabling function, the disabling element is enabled
again. The disabling element waits for the next telegram at the input or for the next
cycle of the configured delay times.
The telegram polarity of the disabling object can be configured.
The transmission behaviour of the disabling element output can be configured.
Heating actuator 6-gang with controller | Order no. 2139 00 | 21393100
Result
OFF telegrams are filtered and not forwarded to
the output. ON telegrams are forwarded to the
output unchanged.
ON telegrams are converted to OFF telegrams
and OFF telegrams are converted to ON tele-
grams and are forwarded to the output.
ON telegrams are filtered and not forwarded to the
output. OFF telegrams are converted to ON tele-
grams and forwarded to the output.
OFF telegrams are filtered and not forwarded to
the output. ON telegrams are converted to OFF
telegrams and forwarded to the output.