Notes On Software - Gira KNX 2139 00 Product Documentation

Heating actuator 6-gang with controller
Table of Contents

Advertisement

Notes on software

7
Notes on software
Unloading the application program
The application program can be unloaded with the ETS. In this case, all valve outputs
of the product are switched off. Manual operation is possible.
ETS project design and commissioning
For project design and commissioning of the device, ETS5 version 5.7.7 or higher or
ETS6 version 6.0.3 or higher is required.
Safe-state mode
If the device does not work properly - for instance as a result of errors in the project
design or during commissioning - the execution of the loaded application program
can be halted by activating the safe-state mode. In safe-state mode, activation of the
valve outputs via the KNX or manual operation is not possible. The room temperature
controllers also have no function. The actuator remains passive in safe-state mode,
since the application program is not being executed (state of execution: Terminated).
Only the system software is still functional so that the ETS diagnosis functions and
also programming of the device continue to be possible.