Room temperature controller | Operating mode and setpoints
T
Comfort setpoint cooling
or
T
Comfort setpoint cooling
The standby and night setpoint temperatures are derived after the configured in-
crease temperatures from the comfort setpoint temperature (basic setpoint). The heat
protection is intended to ensure that the temperature does not exceed the maximum
permissible room temperature in order to protect system components. For this
reason, the heat protection temperature (default: +35 °C) should be set to a higher
value than the night temperature. In principle, however, it is possible to select heat
protection temperature values between +7.0 °C and +45.0 °C. The possible range of
values for a setpoint temperature is bounded by the heat protection temperature in
the upper range.
The level offset configured in ETS will be additionally considered in a two-level cool-
ing mode (see figure 39).
Image 39: Setpoint temperatures in the operating mode "Basic and additional cool-
T
Comfort setpoint basic level cooling
T
Standby setpoint basic level cooling
T
Comfort setpoint cooling
or
T
Comfort setpoint basic level cooling
T
Night setpoint basic level cooling
T
Comfort setpoint cooling
Setpoints for the "heating and cooling" operating mode
Heating actuator 6-gang with controller | Order no. 2139 00 | 21393100
≤ T
Standby setpoint cooling
≤ T
Night setpoint cooling
≤ T
Comfort setpoint additional level cooling
≤ T
Standby setpoint additional level cooling
≤ T
Standby setpoint cooling
≤ T
Comfort setpoint additional level cooling
≤ T
Night setpoint additional level cooling
≤ T
Night setpoint cooling
ing"