Room temperature controller | Operating mode and setpoints
Object no.
343, 393,
443, 493,
543, 593,
643, 693,
743, 793,
843, 893
2-byte object for the output of the current basic setpoint. Depending on the operating
mode, the possible range of values is limited by the configured frost protection and/
or heat protection temperature.
The temperature value is always output in the format "°C".
After mains voltage return or an ETS programming operation (controller reset), the
current basic setpoint temperature is transmitted via this object.
Function: relative setpoint temperature shift via direct temperature value
Object no.
346, 396,
446, 496,
546, 596,
646, 696,
746, 796,
846, 896
2-byte object for setting a basic setpoint shifting, e.g. via a controller extension. The
value of a counter value in the communication object is dependent on the configured
setpoint shift value (0.1 K or 0.5 K). The value "0" means that no shift is active . The
value is depicted in a double complement in the positive and negative direction.
In case the limits of the value range are exceeded by the preset external value, the
controller will automatically reset the received value to the minimum and maximum
limits.
Object no.
345, 395,
445, 495,
545, 595,
645, 695,
745, 795,
845, 895
2-byte object for giving feedback on the current setpoint shift for evaluation, e.g. by a
controller extension. The value "0" means that no shift is active . The value is depic-
ted in a double complement in the positive and negative direction.
After mains voltage return or an ETS programming operation (controller reset), the
current value for the basic setpoint shift is transmitted via this object. Since the value
for the basic setpoint shift is stored exclusively in volatile memory, the shift is always
"0" immediately after a mains voltage return or an ETS programming operation.
Function: relative setpoint temperature shift via counter value x step width
Heating actuator 6-gang with controller | Order no. 2139 00 | 21393100
Function
Setpoint temperat-
ure - Basic value -
Status
Function
Setpoint temperat-
ure - Shift
Function
Setpoint temperat-
ure - Shift - Status
Name
RTC x - Output
Name
RTC x - Input
Name
RTC x - Output
Type
DPT
Flag
2 bytes 9,001
C, R, -, T, A
Type
DPT
Flag
2 bytes 9,002
C, -, W, -, U
Type
DPT
Flag
2 bytes 9,002
C, R, -, T, A